Description

Shell DIALA S4 ZX-I

Premium Electrical Insulating Oil · GTL Technology · Transformer Oil

Product Description

Shell Diala S4 ZX-I is a premium, inhibited electrical insulating oil designed for power, transmission and distribution transformers. Manufactured using Shell's gas-to-liquid (GTL) technology, it is based on highly refined, essentially sulphur-free base oils that provide consistent composition, excellent low-temperature fluidity and high oxidation stability.

The oil is designed to protect transformer insulation systems, support efficient heat transfer and reduce the risk of corrosive sulphur-related damage. It is free from polychlorinated biphenyls (PCBs), dibenzyl disulphide (DBDS) and metal passivator additives. Shell also describes the product as readily biodegradable.

Features and Benefits

  • Excellent oxidation stability: Helps extend oil service life and reduce the ageing of paper insulation.

  • High dielectric strength: Provides electrical insulation for transformer components.

  • Low-temperature performance: Maintains excellent fluidity in cold operating conditions.

  • Copper corrosion protection: Meets relevant corrosive sulphur test requirements.

  • Effective heat transfer: Helps dissipate heat generated during transformer operation.

  • Consistent composition: GTL base-oil technology supports reliable and consistent product quality.

  • Low sulphur content: Helps minimise the risk of sulphur-related corrosion.

  • Environmental properties: Readily biodegradable, according to Shell's product information.

    Applications

    • Power transformers.

    • Transmission and distribution transformers.

    • High-voltage electrical transformers.

    • Industrial transformer installations.

    • Transformers operating in cold climates.

    • Electrical equipment requiring an inhibited insulating oil meeting the relevant IEC 60296 requirements.

    Specifications and Approvals

    • IEC 60296, Edition 5 (2020): Type A, inhibited high-grade insulating oil.

    • IEC 60296, Edition 4 (2012): Table 2 transformer oil, including Section 7.1 requirements for higher oxidation stability and low sulphur content.

    • Designed to meet relevant corrosive sulphur test requirements, including DIN 51353, IEC 62535 and ASTM D1275

      Typical Physical Characteristics

      Property

      Typical value

      Test method

      Appearance

      Clear, free from sediment and suspended matter

      IEC 60296

      Density at 20°C

      805 kg/m³

      ISO 3675

      Kinematic viscosity at 40°C

      9.8 mm²/s

      ISO 3104

      Kinematic viscosity at −30°C

      438 mm²/s

      ISO 3104

      Flash point, PMCC

      191°C

      ISO 2719

      Pour point

      −45°C

      ISO 3016

      Neutralisation value

      Less than 0.01 mg KOH/g

      IEC 62021-1

      Total sulphur content

      Less than 0.001% by mass

      ISO 14596

      Breakdown voltage, untreated

      50–60 kV

      IEC 60156

      Breakdown voltage, after treatment

      78 kV

      IEC 60156

      Dielectric dissipation factor at 90°C

      0.001

      IEC 60247

      Interfacial tension

      51 mN/m

      IEC 62961

      Water content, drums/IBC

      14 mg/kg

      IEC 60814

      Copper corrosion

      Not corrosive

      DIN 51353

      Storage and Handling

      • Store in clean, dry and sealed containers.

      • Protect the oil from moisture, dust and other contaminants.

      • Use clean, dry transfer equipment to preserve dielectric performance.

      • Follow the transformer manufacturer's filling, filtration and dehydration requirements.

      • Test the oil periodically during service to monitor moisture, acidity, dielectric strength and oxidation condition.

      Health and Safety

      Consult the current Safety Data Sheet (SDS) before handling. Avoid prolonged skin contact and use suitable protective gloves when handling used oil. Clean up spills promptly and prevent oil from entering drains, soil or waterways. Dispose of used insulating oil through an authorised waste-management contractor.

      Product Category

      Premium inhibited, readily biodegradable electrical insulating oil for transformers.

      Main Applications

      Power, transmission and distribution transformers requiring high dielectric strength, excellent oxidation stability, low-temperature performance and compliance with the applicable IEC 60296 insulating-oil requirements.